3.5 Stopping
To stop the compressor manually for short periods, the following procedure should be used:
A Flip the compressor’s manual unloader to the vertical position to unload the LP suction valve.
B Open the drain valves.
C Stop the compressor.
When stopping the compressor before prolonged downtime, use the following procedure:
A Drain old oil, clean the crankcase sump and fill with new oil.
B Apply a suitable corrosion inhibiting oil to the compressor valves, non-return valves, cylinder walls and
open surfaces of the crankshaft.
C If there is a danger of frost, drain the cooling water.
D Set the manual unloader in the horizontal position so that there is no load on the compressor’s suction
valve.
E Turn over the compressor by hand once a week.
F The starter panel and other electrical equipment must be similarly protected against corrosion damage.